CRITERIA |
CLASS 10 |
CLASS 100 |
CLASS 1000 |
CLASS 10,000 |
|
AIR CHANGES PER
HR/MIN |
600/HR 10/MIN |
300 - 480/HR 5-8 MIN |
180/HR 3/MIN |
60/HR 1/MIN |
|
FILTER COVERAGE |
100% |
50 - 70% |
20 - 30% |
7 - 15% |
|
CFM PER SQ. FT. |
90 |
36 - 65 |
18 - 32 |
9 - 16 |
|
FILTER EFFICIENCY |
99.9997% (5 - 9 ULPA) |
99.99% (4 - 9
HEPA) |
99.99% (4 - 9 HEPA) |
99.97% (3 - 9 HEPA) |
|
TYPE
OF CEILING
|
FLOWSTAR TRAY
FLOWSTAR
T-BAR CONVENTIONAL CLASS 10 T-BAR
GEL SEAL |
FLOWSTAR TRAY FLOWSTAR
T-BAR CONVENTIONAL CLASS 10 T-BAR GEL SEAL
OR GASKETED |
FLOWSTAR TRAY FLOWSTAR
T-BAR CONVENTIONAL T-BAR GASKETED |
FLOWSTAR TRAY FLOWSTAR
T-BAR CONVENTIONAL T-BAR GASKETED |
|
LIGHT
FIXTURE
|
2' X 4'
CLEANROOM FIXTURE OR TEARDROP |
2' X 4' CLEANROOM FIXTURE CLASS 100 |
2' X 4' CLEANROOM FIXTURE CLASS 1000 |
2' X 4' CLEANROOM FIXTURE
OR STANDARD FIXTURE |
|
CEIL PANELS
|
CLASS 10 VINYL OR EPOXY PAINTED |
CLASS 100 CLEANROOM TILE |
CLEANROOM TILE |
CLEANROOM TILE |
|
WALL
SYSTEM
|
ALUMINUM/ POWDER COAT GLASS OR
LEXAN PRESSURE LAMINATE |
ALUMINUM/ POWDER COAT GLASS OR
LEXAN PRESSURE LAMINATE |
ALUMINUM/ POWDER COAT GLASS OR
LEXAN PRESSURE LAMINATE |
SKINNED OR PAINTED SHEETROCK
PLEXIGLAS |
|
AIR RETURN
|
LOW WALL, RAISED
FLOOR OR TRENCHES |
LOW WALL OR RAISED
FLOOR |
LOW
WALL
|
LOW WALL OR CEILING |
|
FLOOR COVERING |
SHEET VINYL (WELDED) OR POURED EPOXY |
TILE, SHEET VINYL
OR POURED
EPOXY |
TILE, SHEET VINYL
OR POURED
EPOXY |
TILE OR SHEET
VINYL |
|
FLOOR BASE |
COVE |
COVE OR TOP SET
BASE |
COVE OR TOP SET
BASE |
COVE
OR TOP SET BASE |
|
REV
3.28.02 |